Vortex Flowmeter Common Faults and Treatments

Vortex flowmeters are simple to produce and cost-effective. They have been used by many customers. The technical Xiaobian of Shunda Flowmeter has been working on vortex flowmeters for many years and has summarized its common faults and treatment methods for your reference:

1. After the power is turned on, no secondary instrument is displayed

Analysis of the reasons for the power supply wiring error or power disconnection; wiring voltage greater than 220V, electric furnace burnout; supply voltage and the instrument requires the supply voltage does not match; sensor failure or amplifier board failure; the road is too small or no flow in the pipeline. The solution is to check the wiring and correct the wiring; if it is damaged, find the damaged parts, replace the original parts; supply the power supply as required; replace the faulty parts of the secondary meter; adjust the flow of the pipeline.

2. Signal output when there is no flow

Analysis of Causes An interference signal is introduced into the shield of the instrument lead or poor grounding; there is interference with strong electrical equipment or power lines around the instrument; the pipeline is strongly shaken. The solution is to strengthen the lead shielding to ensure that the line is well grounded; to keep the meter away from sources of interference; to jump high to trigger levels or to reduce shocks.

3. Indication error deviation is too large and repeatability is too large

The reason is that the vortex of the primary component is damaged; the lengths of the upstream and downstream straight sections are not enough; the instrument constant K is only set incorrectly; the probe is heavily contaminated; the fluid disturbance in the pipeline is too large. The solution is to replace the vortex generator; change the installation location; recalibrate the meter to obtain the correct meter constant K; clean the probe; replace the installation site and increase the inlet pressure.

4 flow is not accurate, and the process parameters vary widely

The reason analysis was that the process parameters were entered incorrectly; the instrument range did not meet the actual flow requirements. The solution is: correctly enter the instrument parameters; adjust the process or select the instrument that fits the actual flow range.

5. Remote signal output is abnormal

The reason analysis is that if it is a frequency or pulse signal output, the receiving circuit is compatible with the output circuit; if it is (4 ~ 20) mA current output, the flow setting range does not correspond to the output current. The solution is an external electrical component (such as a resistor in series with a certain resistance) to make the output and input circuits compatible; the parameter settings for flow upper and lower limit values ​​correspond to 4mA and 20mA.

The above is an introduction to the common faults and treatment methods of vortex flowmeters. We hope that we can provide them with help. If you have any other questions or needs related to the flowmeter, you can contact Shunda Flowmeter manufacturers. We will be happy to help you. service.

Medium Frequency Induction Heating Machine

Medium Frequency Heating Machine using the principle of electromagnetic induction, eddy current is generated in the workpiece placed in the induction coil, so that the workpiece is hot and heated to the required temperature. The equipment adopts series resonance or parallel resonance, so the power factor is higher. Compared with the traditional heating method, it has the advantages of high efficiency and less pollution. The Medium Frequency Heating Machine shell is made of high-quality aluminum-zinc-coated plate, which is one of the plates that is not easy to corrode and has strong heat resistance. 304 or 316 stainless steel plate can also be customized according to special needs. Intermediate Frequency Heating Equipment has the advantages of small size, light weight, high efficiency, Simple operation, energy saving and environmental protection, stable operation, fast heating, strong heating penetration,excellent thermal processing quality and favorable environment, is a new generation of metal heating equipment. Intermediate Frequency Heating Equipment Application: Street brazing of copper tubes, composite pot bottom brazing, diamond tool brazing, heat treatment of small workpieces, heating forging of small workpieces, annealing and drawing of stainless steel, electrical and electronic or rotor heating and heat fitting.